5-15
Pt. TYPE: SSIGNAL Description: Alarm Signal (on until silence)
Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
Normal Signal Circuit ON
Normal Signal Circuit OFF
Normal Signal Circuit CODING
Open Signal Circuit TROUBLE T
Short Signal Circuit TROUBLE T
Disable TBL Signal Circuit TROUBLE T
Off Auto TBL Signal Circuit TROUBLE T
Detailed Description: Used for all audible / visible units that are required ON
until the alarm silence key is pressed.
Figure 5-38. SSIGNAL Point Type
Pt. TYPE: RSIGNAL Description: Alarm Signal (on until reset)
Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
Normal Signal Circuit ON
Normal Signal Circuit OFF
Normal Signal Circuit CODING
Open Signal Circuit TROUBLE T
Short Signal Circuit TROUBLE T
Disable TBL Signal Circuit TROUBLE T
Off Auto TBL Signal Circuit TROUBLE T
Detailed Description: Used for any signaling device that is required ON until
the system reset key is pressed.
Figure 5-39. RSIGNAL Point Type
Pt. TYPE: SIGNAL Description: Generic Signal (no default
operation)
Circuit Status LCD Readout (2
nd
line) LED
Normal Signal Circuit ON
Normal Signal Circuit OFF
Normal Signal Circuit CODING
Open Signal Circuit TROUBLE T
Short Signal Circuit TROUBLE T
Disable TBL Signal Circuit TROUBLE T
Off Auto TBL Signal Circuit TROUBLE T
Detailed Description: SMPL is required to turn on a SIGNAL point.
Figure 5-40. SIGNAL Point Type
Continued on next page
Point Type Messages for Signal Points, Continued
Signal Points (continued)