Pt. TYPE: BRELAY Description: Trouble / Supervisory Relay (on
until acknowledge) Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
On Alarm Relay ON
Off Alarm Relay OFF
Alarm Relay CODING
Disabled TBL Alarm Relay TROUBLE T
Off Auto TBL Alarm Relay TROUBLE T
Detailed Description: Used for trouble Relay ON (for Trouble or Supervisory)
until the condition is acknowledged.
Figure 5-55. BRELAY Point Type
Pt. TYPE: DHOLDER Description: Door holder Control
(normally off) Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
On Door Holder ON
Off Door Holder OFF
Door Holder CODING
Disabled TBL Door Holder TROUBLE T
Off Auto TBL Door Holder TROUBLE T
Detailed Description: Used when the auxiliary relay is connected to door
holders. The relay energizes on alarm or on loss of AC Power. Relays stays
energized until reset.
Figure 5-56. DHOLDER Point Type
Pt. TYPE: SVISUAL Description: Visual (on until silence)
Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
On Visual ON
Off Visual OFF
Visual CODING
Disabled TBL Visual TROUBLE T
Off Auto TBL Visual TROUBLE T
Detailed Description: Used on visual alarm device circuits that must be ON
until the alarm silence key is pressed (not supervised).
Figure 5-57. SVISUAL Point Type