5-24
Pt. TYPE: PRIMARY Description: Elevator Capture (primary)
Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
On Pri Elevator Relay ON
Off Pri Elevator Relay OFF
Pri Elevator Relay CODING
Disabled TBL Pri Elevator Relay TROUBLE T
Off Auto TBL Pri Elevator Relay TROUBLE T
Detailed Description: Used for any relay connected to the elevator controls to
provide primary floor elevator capture. By default, these relays pick on any
alarm.
Figure 5-64. PRIMARY Point Type
Pt. TYPE: ALTERN Description: Elevator Capture (alternate)
Circuit Status LCD Readout (2
nd
line) LED
On Alt Elevator Relay ON
Off Alt Elevator Relay OFF
Alt Elevator Relay CODING
Disabled TBL Alt Elevator Relay TROUBLE T
Off Auto TBL Alt Elevator Relay TROUBLE T
Detailed Description: Used for any relay connected to the elevator controls to
provide alternate floor elevator capture.
Figure 5-65. ALTERN Point Type
Pt. TYPE: AHUR Description: AHU On / Off (single relay control)
Operates on General Alarm
Circuit Status LCD Readout (2
nd
line) LED
On AHU Relay ON
Off AHU Relay OFF
AHU Relay CODING
Disabled TBL AHU Relay TROUBLE T
Off Auto TBL AHU Relay TROUBLE T
Detailed Description: Used where one auxiliary relay performs AHU ON and
OFF control.
Figure 5-66. AHUR Point Type
Continued on next page
Point Type Messages for Auxiliary Relay Points, Continued
Auxiliary Relay Points
(continued)