162
TimeHub 5500 TL1 Reference Manual
Keywords
097-55501-02 Issue 5: June 2003
SSSSSSSSSSS SSSS S SSSSS SSSSSSS S SSS S SSSSS S
3
PIRANGE (Pull-In Range)
This keyword controls how far the input can be off from the absolute frequency for
the local oscillator before it is disqualified.
Note:
Because this is over the lifetime of the oscillator, this is not a substitute for
frequency deviation.
The keyword format is:
PIRANGE=<value>
Command Example:
RTRV-EQPT::CLK:SC1056:::PARAMETER=PIRANGE;
Response Example:
SYMMBITS 00-06-18 12:00:57
M SC1056 COMPLD
"CLK::PIRANGE = 4731"
;
Parameter Value Description
<value> 10 to 10000 Range in ppb (parts per billion = parts in 10
9
)