2
TimeHub 5500 TL1 Reference Manual
93
Commands
097-55501-02 Issue 5: June 2003
2
5
3
SSSSSSSSSSSS SSSS S SSSSS SSSSSSS S SSS S SSSSS
Set Attribute
This command
sets the alarm level that an event will generate. The command format
is:
SET-ATTR[-TSG]:::<ctag>::<value>,<event>;
Parameter Value Description
<value> NONE No alarm
NONALM Non-alarmed
MINOR Minor alarm
MAJOR Major alarm
FAIL Critical alarm
<event> CLKGONE The management card cannot detect the presence of the
indicated clock card
CLKFAIL A hardware or firmware failure has occurred on the
indicated clock card
CLKWARM The clock card is warming up, and the card is not yet
active
EXCD24HR The indicated clock card has been in holdover for over 24
h
ECCRDMM A different connector card exists than the one specified
through the TL1 command. Specified outputs have been
disabled
EPROTMM There are less than two output driver cards in the indicated
output pair
NVERROR The non-volatile random access memory has failed on the
indicated card
OPCDFL A hardware or firmware failure has occurred on the
indicated output driver card(s) or active clock card
OPCDNA The clock cards cannot communicate with the indicated
output driver card
OPCDNP The management card cannot detect the presence of a
required output driver card
SNFAIL An alarm signal is present within the shelf that has not been
identified by the card generating the alarm signal
CLKOFFL The indicated clock card is offline