186
TimeHub 5500 TL1 Reference Manual
Keywords
097-55501-02 Issue 5: June 2003
SSSSSSSSSSS SSSS S SSSSS SSSSSSS S SSS S SSSSS S
3
TCONSTSEC (Time Constant for Secondary Oscillator)
This keyword sets the time constant for the secondary oscillator; it applies only to
the clock card with the inferior oscillator when mixed clock oscillator types are
used in the TimeHub 5500 system.
This keyword can be used to set the loop tracking time constant for each input.
The assigned value applies only after the system is fully warmed up. This “slow”
tracking mode has a default value based upon the type of clock card oscillator
used. The time constant can be changed to one of several other values if it is
determined that the default value is not appropriate given the characteristics of the
reference inputs.
The keyword format is:
TCONSTSEC=<value>
Command Example:
RTRV-SYNC::CLK-2:SC1745:::PARAMETER=TCONSTSEC;
Response Example:
SYMMBITS 00-06-18 12:06:40
M SC1745 COMPLD
"CLK-2::TCONSTSEC = 384"
;
Parameter Value Description
<value> 102 Time constant
190
384
1824
24864

Table of Contents

Other manuals for Symmetricom TimeHub 5500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeHub 5500 and is the answer not in the manual?

Symmetricom TimeHub 5500 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeHub 5500
CategoryData Loggers
LanguageEnglish

Related product manuals