TimeHub 5500 TL1 Reference Manual
219
Performance Monitoring
097-55501-02 Issue 5: June 2003
2
5
3
SSSSSSSSSSSS SSSS S SSSSS SSSSSSS S SSS S SSSSS
44
Changing (cont’d)
Individual Input Ports
To specify measurement properties for a single input port of a clock card, the
command format is:
ED-SYNC[-TSG]:[<tid>]:CLK-a:<ctag>:::
<montype>=THR-a&CRI-a&RPT-a&PM-a&GOOD-a;
Parameter Value Variables Description
<montype> FFOFF-a a = 3S, 12S, 48S,
192S, 768S, 3072S
FFOFF monitored type, where a is the
averaging time interval in seconds
LMRTIE-a a = 1S, 1M, 15M,
30M, 1H, 2H, 8H,
24H
LMRTIE monitored type, where a is the
observation time interval in seconds (S),
minutes (M), or hours (H)
MRTIE-a a = 1S, 1M, 15M,
30M, 1H, 2H, 8H,
24H
MRTIE monitored type, where a is the
observation time interval in seconds (S),
minutes (M), or hours (H)
SPRD-a a = 3S, 12S, 48S,
192S, 768S, 3072S
SPRD monitored type, where a is the
averaging time interval in seconds
TDEV-a a = 1S, 4S, 16S, 64S,
256S, 1024S
TDEV monitored type, where a is the
averaging time interval in seconds
TIE-a a = 1S, 1M, 15M,
30M, 1H, 2H, 8H,
24H
TIE monitored type, where a is the
observation time interval in seconds (S),
minutes (M), or hours (H)
THR-a a = 0 ns to 1,900,000,000 ns Threshold value, in ns, for LMRTIE and MRTIE
monitored types
a = 0 ppm to 7,300,000 ppm Threshold value, in ppm, for SPRD and FFOFF
monitored types
a = 0 ns to 800,000 ns Threshold value, in ns, for TDEV monitored
type
RPT-a a = Y or N Indicates whether an event is generated (Y) or
not generated (N) when a threshold is
crossed
PM-a a = Y or N Automatically displays (Y) or does not
automatically display (N) each new
measurement as it occurs
GOOD-a a = 1 to 15 Number of consecutive good measurements
that must occur following a bad measurement
before an input signal can be qualified and
for the INMEAS event to be cleared

Table of Contents

Other manuals for Symmetricom TimeHub 5500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeHub 5500 and is the answer not in the manual?

Symmetricom TimeHub 5500 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeHub 5500
CategoryData Loggers
LanguageEnglish

Related product manuals