99
APPENDICES
APPENDIX B - ERROR CODES
ERROR CODE DESCRIPTION SEE PARAMETER
1 Invalid parameter number for Calibration Mode Calibration Mode
2 Invalid Graduation size 3
3 Invalid Decimal Position 2
4
Parameter value must be 1 for ‘ON’ or 0 for ‘OFF’
22
5 Push to Zero Window must be 0-99 21
8 Only 1 will reset Span Table 15
10 IZSM value can be 1 for ON and 0 for OFF 45
12 Motion settle time out of range (1-50) 24
13 Power on units may only be 0=lb, 1=kg. 6
14 Invalid Time entry HH.MM.SS 80
15 Invalid Date entry YY.MM.DD 81
16 Motion value is out of range (1-10) 5
17 Press tare to increment span table, any other key invalid 16
17 Press tare to decrement span table, any other key invalid 17
19 Span table cannot be decremented past 1 17
23 Invalid Serial Port speed setting 30, 32
24 Invalid Serial Port Parity parameter 27, 31, 33
25 Cannot increment Span Table any further 16
26 Entered offset larger than Capacity 25
28 Power on Zero warning 0=Off, 1=On 9
29 Channel enable is 0=Off and 1=On 98
30 Only 1 will set the deadload 12
31 Sound Volume can be between 0-3 28
32 Keypress feedback can be 0=OFF or 1=ON 29
37 Channel 1 cannot be disabled 98
38 Invalid Print Select Function Number Normal Weighing Mode
40 Scale channel is not enabled Normal Weighing Mode
41 Pushbutton Tare is invalid (Over, Motion, or disabled) Normal Weighing Mode
42 Keyboard tare available on channel 1 only Normal Weighing Mode
43 Tare greater than capacity Normal Weighing Mode
46 Invalid Entry (Parameter 26 - Values of 0, 1 & 80 are acceptable) 26
47 Bad Clock Mode (0-2) 83
48 Invalid Main Filter Value 41
49 Invalid Output String Format 34
49 Invalid Faststep Threshold Value 42
50 Zero tracking must be 1-99 or 100, 200, 300. 23