SETPOINT SET-UP PARAMETERS
SETPOINT CONTROL MASK - PARAMETER 57
Description: Controls how each of the 6 Setpoints will function. This is a 6 digit
parameter with each digit representing one of the Setpoints.
The left most digit represents Setpoint # 6 while the
rightmost digit represents Setpoint # 1.
The value of each digit represents the function of that particular Setpoint.
PARAMETER VALUE SETPOINT FUNCTION
0 (default) Do not modify.
1 Energize output when weight < Setpoint value.
2 Energize output when weight >= Setpoint value.
3 Disable the Setpoint.
A common Setpoint Mask may look like this:
When entering the control mask, 6 digits must be entered. The first
digit entered represents Setpoint 6 of 6. The last digit entered
represents Setpoint 1 of 6.
A dash (-) in a digit indicates the Setpoint is not assigned to this
scale channel. It is either not used, or is being used by another
scale channel.
Remember: It is very important to enter ā€œ0ā€ for a Setpoint that you
do not want to modif