HIGH SPEED DIGITAL WEIGHT INDICATORS
22
M2000A ANALOG LOADCELL WIRING
Loadcell connections are labeled as follows:
LABEL CONNECTION
- EXC Negative Excitation
- SNS Negative Sense
+ SNS Positive Sense
+ EXC Positive Excitation
SHLD Loadcell Shield
- SIG Negative Signal
+ SIG Positive Signal
SCALE SYSTEMS WITH ONE LOADCELL ONLY
The Loadcell is wired directly to the M2000A using a 7 pin terminal connector.
The connector can be unplugged from the M2000 to make wiring easier.
• Pass the loadcell cable through the strain-relief, into the enclosure (Not
required for Slimline models).
• Terminate the loadcell wires, according to the Loadcell Connection table
above. Make sure each wire is securely fastened in the appropriate
position.
• Plug the connector into the appropriate terminal (Scale Channel).
• Re-assemble the M2000 enclosure as necessary.
-EXC
-SNS
+EXC
SHLD
-SIG
+SIG
+SNS
CHANNEL 1
BE SURE TO CHECK THE LOADCELL MANUFACTURER’S
INSTRUCTIONS FOR THE CORRECT WIRE COLOUR CODE.