6-3
Reboot Options
• IntervalAfterFailedPing: Determines how often the Ping command will be sent
after a previous Ping command receives no response. (Default = 10 Seconds)
• PingDelayAfterPNAAction: Determines how long the RSM-8R8 Series unit will
wait to send additional Ping commands, after a Ping-No-Answer Reboot has been
initiated. Typically, this option is used to allow time for a device to fully "wake up"
after a Ping-No-Answer Reboot before attempting to Ping the device again.
(Default = 15 Minutes)
• ConsecutiveFailures: Determines how many consecutive failures of the Ping
command must be detected in order to initiate a Ping-No-Answer Reboot. For
example, if this value is set to "3", then after three consecutive Ping failures, a
Ping-No-Answer Reboot will be performed. (Default = 5)
• Reboot: Enables/Disables the Ping-No-Answer Reboot function for the specified
IP address. When this item is disabled, the RSM-8R8 Series unit will not reboot the
specified outlet(s) when a Ping-No-Answer is detected. However, RSM-8R8 Series
units will continue to notify you via Email, Syslog Message and/or SNMP Trap,
providing that parameters for these functions have been defined as described in
Section 5.9 and the Ping-No-Answer Answer alarm has been enabled as described
in Section 7.4. (Default = No)
Notes:
• InorderforEmail/TextMessageNotificationtofunction,youmustfirstdefine
Email/TextMessageparametersasdescribedinSection5.9.11.
• InorderforSyslogMessageNotificationtofunction,youmustfirstdefinea
SyslogAddressasdescribedinSection5.9.2.
• InorderforSNMPTrapNotificationtofunction,youmustfirstdefineSNMP
parametersasdescribedinSection5.9.7.
• PNAAction: Determines how RSM-8R8 Series units will react when the IP address
fails to respond to a ping. RSM-8R8 Series units can either continuously reboot the
specified outlet(s) and send notification until the IP address responds and the Ping-
No-Answer Reboot is cleared (Continuous Alarm/Reboot), or reboot the specified
outlet(s) and send notification only once each time the Ping-No-Answer Reboot is
initially triggered (Single Alarm/Reboot.) (Default = Continuous Alarm/Reboot)
• PlugAccess: Determines which outlet(s) will be rebooted when this IP address
for this Ping-No-Answer operation does not respond to a Ping command. Note
that in the Text Interface, Plug Access is defined via a separate submenu; in the
Web Browser Interface, Plug Access is defined via a drop down menu, which may
be accessed by clicking on the "plus" sign in the "Configure Plug Access" field.
(Default = undefined)
• PlugGroupAccess: Determines which Plug Group(s) the Ping-No-Answer
Reboot for this IP Address will be applied to. Note that in the Text Interface, Plug
Group Access is defined via a separate submenu; in the Web Browser Interface,
Plug Group Access is defined via a drop down menu, which may be accessed by
clicking on the "plus" sign. (Default = undefined)