7-4
Alarm Configuration
LoadShedding: Provides access to a submenu which is used to configure
and enable the Load Shedding feature for the Over Current Alarm. When Load
Shedding is enabled and properly configured, the RSM-8R8-CM will switch
user-selected plugs On or Off whenever the current load exceeds the Alarm
Set Threshold value. If the Auto Recovery feature is enabled, the RSM-8R8-CM
can also return these user-selected plugs to their prior status when current load
falls below the Alarm Clear Threshold value. For more information on the Load
Shedding Feature and Auto Recovery, please refer to Section 7.1.1.
7.1.1. Over Current Alarms - Load Shedding and Auto Recovery
The Load Shedding feature is used to switch specific, user-defined, non-essential plugs
On or Off whenever current load exceeds the Alarm Set Threshold value. This allows
the RSM-8R8-CM to automatically shut Off plugs in order to reduce current load when
the load approaches user-defined critical levels. When the Auto Recovery feature
is enabled, the RSM-8R8-CM can also automatically "undo" the effects of the Load
Shedding feature when current load again falls to a user-defined non-critical level.
Together, the Load Shedding and Auto Recovery features allow the RSM-8R8-CM to
shut off power to non-essential devices when the current load is too high, and then
switch those same non-essential devices back On again when the load falls to an
acceptable level.
The Load Shedding Configuration Menus allow you to define the following parameters:
Notes:
CurrentandPowerMonitoringfeaturesarenotavailableonstandardTSM
unitsorstandardRSMunits.
• TheLoadSheddingConfigurationMenusfortheOverCurrentAlarmsoffer
essentiallythesamesetofparameters,butparametersdefinedforeach
alarmareseparateandunique.Forexample,parametersdefinedforOver
Current(Initial)AlarmLoadSheddingwillnotbeappliedtoOverCurrent
(Critical)AlarmLoadSheddingandviceversa.
Enable: Enables/Disables Load Shedding for the corresponding alarm. When
enabled, the RSM-8R8-CM will switch the user specified plugs whenever current
load exceeds the Alarm Set Threshold value. (Default = Off)
PlugState: Determines whether the selected plugs/plug groups will be switched
On or Off when Load Shedding is enabled and current load exceeds the user-
defined Alarm Set Threshold. For example, if the Plug State is "Off", then plugs
or plug groups will be switched Off when the Alarm Set Threshold is exceeded.
(Default = Off)