9-12
Operation
9.2. Controlling Power - Web Browser Interface (RSM-8R8 Series Only)
Note:PowerswitchingandrebootfunctionsareonlyavailableonRSM-8R8
Seriesunits.StandardTSMSeriesunitsandstandardRSMSeriesunitsdonot
supportpowercontrolfunctions.
When using the Web Browser Interface, switching commands are invoked via the Plug
Control Screen and Plug Group Control Screen.
9.2.1. The Plug Control Screen - Web Browser Interface
Note:PowerswitchingandrebootfunctionsareonlyavailableonRSM-8R8
Seriesunits.StandardTSMSeriesunitsandRSMSeriesunitsdonotsupport
powercontrolfunctions.
The Plug Control Screen lists the On/Off status of the RSM-8R8 Series unit's Switched
Outlets and is used to control switching and rebooting of the outlets. To invoke power
switching commands, access command mode and then click on the "Plug Control" link
on the left hand side of the screen to display the Plug Control Screen. When the Plug
Control Screen appears, click the down arrow in the "Action" column for the desired
outlet(s), then select the desired switching option from the dropdown menu and click on
the "Confirm Plug Actions" button.
When the "Confirm Plug Actions" button is pressed, the RSM-8R8 Series unit will display
a screen which lists the selected action(s) and asks for confirmation before proceeding.
To implement the selected action(s), click on the "Execute Plug Actions" button. The
RSM-8R8 Series unit will display a screen which indicates that a switching operation is in
progress, then display the Plug Status screen when the command is complete. At that
time, the Status Screen will list the updated On/Off status of each plug.
Notes:
• Whenswitchingandrebootoperationsareinitiated,Boot/SequenceDelay
timeswillbeappliedasdescribedinSection5.7.
• Ifaswitchingorrebootcommandisdirectedtoaplugthatisalreadyin
theprocessofbeingswitchedorrebooted,thenthenewcommandwillbe
placedinaqueueuntiltheplugisreadytoreceiveadditionalcommands.
• IftheStatuscolumninthePlugControlScreenincludesanasterisk,this
meansthattheoutletisbusycompletingapreviouslyinvokedcommand.
• WhenthePlugControlScreenisdisplayedbyanaccountthatpermits
AdministratororSuperUserlevelcommands,allswitchedoutletswillbe
shown.
• WhenthePlugControlScreenisdisplayedbyanaccountthatpermitsUser
orViewOnlycommandaccess,thescreenwillonlyincludetheswitched
outletsthatarespecificallyallowedbytheaccount.