7-6
Alarm Configuration
7.2. The Over Temperature Alarms
The Over Temperature Alarms can inform you when temperatures inside your equipment
rack reach or exceed user specified trigger levels. There are two separate Over
Temperature Alarms; the Initial Threshold alarm and the Critical Threshold Alarm.
Typically, the Initial Threshold alarm is used to provide notification when temperatures
reach a point where you might want to investigate, whereas the Critical Threshold alarm
is used to provide notification when temperatures approach a level that may harm
equipment or inhibit performance. The trigger for the Initial Threshold alarm is generally
set lower than the Critical Threshold alarm.
Notes:
• InorderfortheTSM/RSMtoprovidealarmnotificationviaEmail,
communicationparametersmustfirstbedefinedasdescribedin
Section5.9.11.
• InorderfortheTSM/RSMtoprovidealarmnotificationviaSyslogMessage,
SyslogparametersmustfirstbedefinedandSyslogMessagesmustbe
enabledasdescribedinSection5.9.2.
• InorderfortheTSM/RSMtoprovidealarmnotificationviaSNMPTrap,SNMP
parametersmustfirstbedefined,andSNMPTrapsmustbeenabledas
describedinSection5.9.7.
To configure the Over Temperature Alarms, access the TSM/RSM command mode
using a password that permits Administrator Level commands, and then use the Alarm
Configuration menu to select the desired alarm feature.
Note that both the Initial Threshold menus and Critical Threshold menus offer essentially
the same set of parameters, but parameters defined for each alarm are separate and
unique. Therefore, parameters defined for the Critical Threshold Alarm will not be
applied to the Initial Threshold Alarm and vice versa. Both the Over Temperature (Initial
Threshold) alarm and the Over Temperature (Critical Threshold) alarm offer the following
parameters:
• TriggerEnable: Enables/Disables the trigger for this alarm. When Disabled, this
alarm will be suppressed. (Default = On)
Notes:
• Tocancelanalarmwithoutcorrectingtheconditionthatcausedthealarm,
simplytoggletheTriggerEnableparameterOffandthenbackOnagain.
• TheTriggerEnable,NotifyonClear,EmailMessageandAddress1,2and3
Parametersallinclude"CopytoAllTriggers"optionsthatallowyoutoenable/
disablethecorrespondingparameterforallTSM/RSMalarms.Forexample,
iftheLostCommunicationAlarm'sTriggerEnableparameterissetto"On