7-5
Alarm Configuration
• AutoRecovery: Enables/Disables the Auto Recovery feature for the selected
branch or line. When both Load Shedding and Auto Recovery are enabled, the
RSM-8R8-CM will return plugs to their former On/Off state after current load falls
below the Alarm Clear Threshold value. This allows the RSM-8R8-CM to "undo"
the effects of Load Shedding after current load has returned to an acceptable level.
(Default = Off)
• PlugAccess: Determines which Plug(s) will be switched when current load
exceeds the Alarm Set Threshold and Load Shedding is triggered. For example,
if plugs A1, A2 and A3 are selected, then these plugs will be switched On or Off
whenever current load exceeds the Alarm Set Threshold. (Default = undefined)
• PlugGroupAccess: Determines which Plug Group(s) will be switched when the
Load Shedding feature is triggered. For example, if you have defined a Plug Group
named "test", which includes Plugs B3, B4 and B5, and then selected the "test" Plug
Group via the Plug Group Access parameter, then all of the plugs in the "test" Plug
Group will be switched On or Off whenever the current load exceeds the Alarm Set
Threshold. (Default = undefined)
Note:PlugGroupsmustfirstbedefined(asdescribedinSection5.6)before
theywillbedisplayedintheLoadSheddingmenu'sPlugGroupAccess
submenu.
After setting parameters for a given branch or line, you may also define additional
parameters for other branches or lines (if present) To set Load Shedding parameters
for other branches or lines, return to the Alarm Configuration menu and then repeat the
procedure described in Section 7.1.1.