17-1
17. Command Reference Guide
17.1. Command Conventions
Most commands described in this section conform to the following conventions:
• PowerControlFunctions: Standard TSM Series units and Standard RSM Series
units do not support power control functions. Power reboot and switching functions
are only available on RSM-8R8 Series units.
• ApplyCommandtoAllPorts: When an asterisk is entered as the argument of the
/D (Disconnect) or /E commands (Erase Buffer) the command will be applied to all
ports. For example, to erase all port buffers, type /E * [Enter].
• ApplyCommandtoAllPlugs: (RSM-8R8 Series Units Only) When an asterisk is
entered as the argument of the /ON (Switch Plugs On), /OFF (Switch Plugs Off) or
/BOOT (Reboot Plugs) commands, the command will be applied to all plugs. For
example, to reboot all allowed plugs, type /BOOT * [Enter].
• CommandQueues: (RSM-8R8 Series Units Only) If a switching or reboot
command is directed to a plug that is already being switched by a previous
command, then the new command will be placed into a queue until the plug is
ready to receive additional commands.
• "Busy"Plugs: (RSM-8R8 Series Units Only) If the "Status" column in the Plug
Status Screen includes an asterisk, this means that the plug is currently busy, and
is in the process of completing a previously issued command. If a new command
is issued to a busy plug, then the new command will placed into a queue to be
executed later.
• PlugNameWildCard: (RSM-8R8 Series Units Only) It is not always necessary
to enter the entire plug name. Plug names can be abbreviated in command lines
by entering the first character(s) of the name followed by an asterisk (*). For
example, a plug named "SERVER" can be specified as "S*". Note however, that this
command would also be applied to any other plug name that begins with an "S".
• SuppressCommandConfirmationPrompt: When any command that normally
requires confirmation is invoked, the ",Y" option can be included to override the
Command Confirmation ("Sure?") prompt. For example, to reboot Plug 4 without
displaying the Sure prompt, type /BOOT 4,Y [Enter].
• ConnectedPorts: When two ports are connected, most RSM commands will not
be recognized by either of the connected ports. The only exception is the Resident
Disconnect Sequence (Default = ^X ([Ctrl] plus [X]).)