8-5
The Status Screens
8.6. The Current Metering Status Screen (RSM-8R8-CM Series Only)
The Current Metering Status screen is primarily intended to be used to display up-to-
date readings for Amps, Watts, Voltage and temperature for the RSM-8R8-CM Series
unit. To view the Current Metering Log screen, proceed as follows:
Note:CurrentandPowerMonitoringfeaturesarenotavailableonstandard
TSMunitsorstandardRSMunits.
In addition to displaying the Current Metering Status Screen, the /M command can
also be used to display current, voltage and power readings for each switched outlet
on RSM-8R8-CM Series units. When the /M command is invoked, the command line
can also include arguments that display the status of individual outlets, specific pairs of
outlets or a range of outlets:
/M Displays the Current Metering Status Screen.
/M s Displays current, voltage and power readings for an individual plug or
outlet, where s is the name or number of the desired outlet.
/M s+s Displays current, voltage and power readings for two or more specific
outlets, where s is the number or name of each desired outlet. A plus sign
(+) is entered between each outlet number or name.
/M s:s Displays current, voltage and power readings for a range of outlets, where
s is the number or name of the outlet at the beginning and end of the range
of desired outlets. A colon (:) is entered between the two outlet numbers or
names that mark the beginning of the range and the end of the range.
/M a Displays current, voltage and power readings for Branch A.
/M b Displays current, voltage and power readings for Branch B.
Notes:
• IntheTextInterface,whencurrent,voltageandpowerreadingsaredisplayed
forasingleoutlet,pairofoutletsorrangeofoutlets,readingsforeachoutlet
specifiedwillbedisplayedasthreevaluesseparatedbycommas.Current
willbedisplayedfirst,thenvoltage,thenpower.
• WhenCurrentUsageisreportedasapercentageofmaximumcurrent,the
valueshowwillreflectthepercentageofrealmaximumcurrentused,rather
thanthepercentageofde-ratedmaximumcurrentused.
To display the Current Metering Status Screen, proceed as follows:
• TextInterface: Type /M and press [Enter].
• WebBrowserInterface: Place the cursor over the "Current Metering" link on the
left hand side of the screen. When the fly-out menu appears, click on the "Current
Metering Status" link.