7-14
Alarm Configuration
PingTest: (Text Interface Only) Sends a test Ping command to this IP Address.
Notes:
• InorderforthePingTestfeaturetoworkproperly,yournetworkand/or
firewall,aswellasthedeviceatthetargetIPaddress,mustbeconfiguredto
allowpingcommands.
• AfterdefiningoreditingPingNoAnswerIPAddresses,makecertaintosave
thechangesbeforeproceeding.IntheWebBrowserInterface,clickon
the"AddPingNoAnswer"buttontosaveparameters;intheTextInterface,
pressthe[Esc]keyseveraltimesuntilthe"SavingConfiguration"messageis
displayedandthecursorreturnstothecommandprompt.
7.4.1.2. ConfiguringthePingNoAnswerAlarm-TSMandRSMSeriesUnits
To configure the Ping-No-Answer Alarm, you must access command mode using a
password that permits Administrator Level commands. The Ping-No-Answer alarm
configuration menu offers the following parameters:
TriggerEnable: Enables/Disables the trigger for this alarm. When Disabled, this
alarm will be suppressed. (Default = On)
Notes:
• Inorderforthisalarmtofunction,atleastonetargetIPAddressforthePing
NoAnswerAlarmmustbedefinedasdescribedinSection7.4.1.1.
• Tocancelanalarmwithoutcorrectingtheconditionthatcausedthealarm,
simplytoggletheTriggerEnableparametertoOffandthenbackOnagain.
• TheTriggerEnable,NotifyonClear,EmailMessageandAddress1,2and3
Parametersallinclude"CopytoAllTriggers"optionsthatallowyoutoenable/
disablethecorrespondingparameterforallTSM/RSMalarms.Forexample,
ifthePingNoAnswerAlarm'sTriggerEnableparameterissetto"On(Copyto
AllTriggers),thenallotherTSM/RSMalarmswillalsobeenabled.
ResendDelay: Determines how long the TSM/RSM will wait to resend an email
message generated by this alarm, when the initial attempt to send the notification
was unsuccessful. (Default = 60 Minutes)
NotifyUponClear: When this item is enabled, the TSM/RSM will send additional
notification when the situation that caused the alarm has been corrected. For
example, when Notify Upon Clear is enabled, the TSM/RSM will send initial
notification when it detects that a Ping command has failed, and then send a
second notification when it determines that the IP address is again responding to
the Ping command. (Default = On)