7-7
Alarm Configuration
• AlarmSetThreshold: The trigger level for this alarm. When temperature exceeds
the Alarm Set Threshold, the TSM/RSM can send an alarm (if enabled) and/or begin
Load Shedding (if enabled.) For more information on Load Shedding, please refer
to Section 7.2.1. (Initial Threshold: Default = 90°F or 32°C, Critical Threshold:
Default = 100°F or 38°C)
Note:TheAlarmSetThresholdvaluemustbegreaterthantheAlarmClear
Thresholdvalue.TheTSM/RSMwillnotallowyoutodefineanAlarmClear
ThresholdvaluethatishigherthantheAlarmSetThreshold.
• AlarmClearThreshold: Determines how low the temperature must drop in order
for the Alarm condition to be cancelled and for Auto Recovery (if enabled) to
occur. For more information on Load Shedding and Auto Recovery for the Over
Temperature Alarm, please refer to Section 7.2.1. (Initial Threshold: Default = 80°F
or 27°C, Critical Threshold: Default = 90°F or 38°C)
Note:TheSystemParametersmenuisusedtosetthetemperatureformatfor
theTSM/RSMunittoeitherFahrenheitorCelsiusasdescribedinSection5.3.
• ResendDelay: Determines how long the TSM/RSM will wait to resend an email
message generated by this alarm, when the initial attempt to send notification was
unsuccessful. (Default = 60 Minutes)
• NotifyUponClear: When this item is enabled, the TSM/RSM will send additional
notification when the situation that caused the alarm has been corrected. For
example, when Notify Upon Clear is enabled, the TSM/RSM will send initial
notification when it detects that the temperature has exceeded the trigger value,
and then send a second notification when it determines that the temperature has
fallen below the trigger value. (Default = On)
• EmailMessage: Enables/Disables email notification for this alarm. (Default = On)
• Address1,2,and3: These parameters are used to select which of the three email
addresses, defined via the "Email Messages" menu (see Section 5.9.11,) will receive
the email alarm notification messages generated by this alarm. The Address
parameters can be used to select one, or any combination of the addresses defined
via the Email Messages menu. (Default = All On)
Note:IfEmailaddresseshavebeenpreviouslydefined,thenthetextunderthe
parameterswilllistthecurrent,userdefinedemailaddresses.
• Subject: This parameter is used to define the text that will appear in the "Subject"
field for all email notification messages generated by this alarm. (Default = "Alarm:
Over Temperature (Initial)" or "Alarm: Over Temperature (Critical)")