EasyManuals Logo

Automation Direct DURApulse GS4 User Manual

Automation Direct DURApulse GS4
542 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
Page 4–76
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Multi-Function Output Terminal Function Settings (P3.17~P3.31) (continued)
Setting: Function Function Description
42: Brake Released at Stop
(Brake Engaged During Decel)
This function is typically used in conjunction with a mechanical brake�
When drive stops, the corresponding Multi-Function Output terminal will be ON
if the frequency is less than P3�53� After it is ON, the output will turn OFF when
brake delay time exceeds P3�51�
Multi-function
Output
P3.17~P3.33
= 42
Run
Output
Frequency
Output
Frequency
< P3.53
P3.51
RUN
Note: With a long deceleration and a short brake time, the output could energize
(for P3.51) and de-energize before the ramp is complete.
43: RS485 Digital Output
Enables user control of an output via RS-485� When the MFO is set to 43,
writing to the correct bit in address 2640h (Modbus 49793) will turn on the
associated output� This address will reset to zero when written to via RS-485
(but the output will stay ON because the bit was set)� Digital Output Status
should always be read from P3�47 (Modbus decimal address 40816)�
Bit 0 1 2 3 4 5 6 7 8 9
Out R1 R2 xx DO1 DO2 DO10 DO12 DO13 DO14 DO15
Example:
Set P3�17 = 43 (Sets R1 to RS485 Digital Output)
Write a 1 to Bit 0 of 49793� R1 will turn ON�
Bit 0 of 49793 will read 0 (49793 auto-resets to 0)�
Bit 0 of 40816 (P3�47 Digital Output Status) will read 1�
Write a 0 to Bit 0 of 49793 to turn R1 OFF
44: COMM Card Digital Output
Allows user to control Digital Outputs via Ethernet Comm Card� Each output
has a corresponding bit in 40793� Only writes from the Ethernet card will cause
the output to turn ON if #44 is selected� The value in 40793 is maintained when
written to over Ethernet�
45: Fire Mode Indication
An activation of setting 45 indicates fire mode is active� Requires Multi-Function
Input P3�03~3�16 configured for 40: Fire Mode with RUN Command, or 41: Fire
Mode without RUN Command� Requires Fire Mode P6�55 to be enabled�
When the DI for Fire Mode turns ON, the DO associated with this input will also
turn ON� The output is not retentive; the output turns ON and OFF with the Fire
Mode DI�
46: Fire Bypass Indication
Requires Fire Mode Enable Bypass P6�57 to be enabled� The bypass will activate
after the Bypass Delay Time� Once Fire Mode input is turned OFF, the bypass
will be turned OFF
Only certain types of faults are able to be bypassed in Fire Mode
The list of fault codes, including which ones can and cannot be bypassed in
Fire Mode, is shown in the "Fault Codes" table in Chapter 6: Maintenance and
Troubleshooting (page 6–16)�
47: Motor #1 Selected
When setting multi-motor circulative function, the Multi-Function Output
terminal will automatically set up P3�17(R1), 3�18(R2), and P3�21(R10)~P3�26(R15)
in accordance with P10�01’s (Number of Connected Motors) setting (page 4–195)�
48: Motor #2 Selected
49: Motor #3 Selected
50: Motor #4 Selected
51: Motor #5 Selected
52: Motor #6 Selected
53: Motor #7 Selected
54: Motor #8 Selected
55: Mtr1/Mtr2 Nameplate Parameters Indicates which motor is selected from P0�10 or MFI setting 14�
56: Safety STO A Normally Open Auxiliary output for STO indication� Not safety rated
(table continued next page)

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals