Chapter 4: AC Drive Parameters
Page 4–183
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P9.08 Restore to Default
R/W 0908 42313
Range/Units (Format: 16-bit binary) Default
0: no function
1: Parameter Lock
2: no function
3: no function
4: no function
5: Reset kWh Display to Zero
6: Reset PLC (clear PLC)
7: no function
8: no function
9: Reset 50Hz Default
10: Reset 60Hz Default
0
When this parameter is set to 1, all parameters except P9.08, P8.06, and P8.07 (Password Set Up)
become read only.
Set P9.08 to 0 before changing other parameter settings.
When set to 5, kWh display value can be reset to 0, even when the drive is operating�
When set to 6, the internal PLC program will be cleared�
When set to 9 or 10, all parameters will be reset to factory settings� If the password is set in P8�07,
input the password set in P8�06 to reset to factory settings�
When set to 6, 9, or 10, power must be cycled on the drive for setting to take effect�
Resets cannot be performed while PLC is running or in stop mode; the PLC must be in Disable
mode�
If an "Err" appears on the keypad after performing a default action, then the default action did not
take affect� The keypad will report back "End" if the default was performed correctly
This parameter does not reset the communication settings inside the Ethernet
communication card. (Any new communication card parameter values must be "pushed"
from the P9 parameters to the card. See P9.64)
Type Hex Addr Dec Addr
P9.09 Block Transfer Data Location 1
* R/W 0909 42314
P9.10 Block Transfer Data Location 2
* R/W 090A 42315
P9.11 Block Transfer Data Location 3
* R/W 090B 42316
P9.12 Block Transfer Data Location 4
* R/W 090C 42317
P9.13 Block Transfer Data Location 5
* R/W 090D 42318
P9.14 Block Transfer Data Location 6
* R/W 090E 42319
P9.15 Block Transfer Data Location 7
* R/W 090F 42320
P9.16 Block Transfer Data Location 8
* R/W 0910 42321
P9.17 Block Transfer Data Location 9
* R/W 0911 42322
P9.18 Block Transfer Data Location 10
* R/W 0912 42323
P9.19 Block Transfer Data Location 11
* R/W 0913 42324
P9.20 Block Transfer Data Location 12
* R/W 0914 42325
P9.21 Block Transfer Data Location 13
* R/W 0915 42326
P9.22 Block Transfer Data Location 14
* R/W 0916 42327
P9.23 Block Transfer Data Location 15
* R/W 0917 42328
P9.24 Block Transfer Data Location 16
* R/W 0918 42329
Range/Units (Format: 16-bit unsigned) Default
0~65535
200
* P9�09~P9�24 can be set in run mode if the corresponding Block Transfer Address Pointer
(P9�69~P9�84) is pointing to a register that allows writes while in run mode�
This block of parameters (P9.09 to P9.24) contains parameter data values. The pointer addresses
for these data are defined in parameters P9.69 to P9.84.
Refer to “Block Transfer Explanation” (page 4–192) for details about transferring blocks of data.
Type Hex Addr Dec Addr
P9.25 reserved
~ 0919 42330

Table of Contents

Other manuals for Automation Direct DURApulse GS4