026-1803 R13 Supervisor I&O User Guide 3 - 11
3.12 Site Supervisor Wiring Examples
Site Supervisor IONet connections must be wired reverse polarity.
For Site Supervisor Serial IONet connections, connect the white wire to the negative terminal and the black wire to the
positive terminal.
For 8RO and MultiFlex RS485 IONet connections, connect the white wire to the positive terminal and the black wire to the
negative terminal.
Connect the shield wire to earth/chassis at the Site Supervisor end of the IONet network segment. DO NOT
connect the shield wire to any connector on the Site Supervisor.
For daisy-chain configurations, terminate devices at the beginning and the end of the network segment. All other devices
in the network segment are not terminated (termination jumpers in the not-terminated position).
Figure 3-17 - Supervisory Controller and MultiFlex Wiring