8.5 Configure a Frequency Output
Use a Frequency Output to report current values of process variables. The frequency varies between 0 Hz and
12500 Hz in proportion to the current value of the assigned process variable. Maximum fault level is 14500 Hz.
8.5.1 Configure Frequency Output Source
Display MenuConfigurationInputs/OutputsChannel BI/O TypeFrequency Output
ProLink III Device ToolsConfigurationI/OChannelsChannel BFrequency Output
Field communicator Device SettingsInputs/OutputsChannelsChannel B
Frequency Output Source specifies the process variable that is reported by the Frequency Output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set Volume Flow Type as
desired: Liquid or Gas Standard Volume.
If you plan to configure an output to report a concentration measurement process variable, ensure that
the concentration measurement application is configured so that the desired variable is available.
Procedure
Set Frequency Output Source as desired.
Postrequisites
If you change the configuration of Frequency Output Source, verify the Frequency Output scaling. The
transmitter automatically loads the most recent values for the scaling parameters, and they may not be
appropriate for your application.
Related information
Configure Frequency Output Scaling
Options for Frequency Output Source
The transmitter provides a basic set of options for Frequency Output Source, plus several application-specific
options. Different communications tools may use different labels for the options.
Process variable
Label
Display PLIII
Standard
Mass flow rate Mass Flow Rate Mass Flow Rate
Volume flow rate Volume Flow Rate Volume Flow Rate
Gas standard volume flow rate GSV Flow Rate Gas Standard Volume Flow Rate
API Referral
Temperature-corrected (standard)
volume flow rate
Referred Volume Flow Volume Flow Rate at Reference
Temperature
Concentration measurement
Standard volume flow rate Standard Vol Flow Volume Flow Rate at Reference
Temperature
Net mass flow rate Net Mass Flow Net Mass Flow Rate
Integrate the meter with the control system Configuration and Use Manual
May2024 MS-00809-0200-1600