Emerson Micro Motion 1600 - 8.6.2 Configure Discrete Output Polarity; 8.6.3 Configure Discrete Output Fault Action

Emerson Micro Motion 1600
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Option Label
State Discrete Output voltage
Display Prolink III
Smart Meter
Verification
Smart Meter
Verification
Meter Verification
Failure
(3)
ON Externally powered: Site-specific
OFF 0 V
Batch Primary Valve Batch Primary Valve Batch Primary Valve ON Externally powered: Site-specific
OFF 0 V
(1) Events configured using the enhanced event model.
(2) Events configured using the basic event model.
(3) The ProLink III v5.0 option is “Meter Verification Failure” for the Discrete Output Source field. This does
match the table entry.
Important
This table assumes that Discrete Output Polarity is set to Active High. If Discrete Output Polarity is set to
Active Low, reverse the voltage values.
Important
Actual flow direction interacts with Sensor Flow Direction Arrow to determine the flow direction that the
transmitter uses in processing. See the following table.
Table 8-3: Interaction between actual flow direction and Sensor Flow Direction Arrow
Actual flow direction
Setting of Sensor Flow Direction
Arrow
Flow direction sent to outputs and
totalizers
Forward (same direction as Flow arrow
on sensor)
With Arrow Forward
Against Arrow Reverse
Reverse (opposite from Flow arrow on
sensor)
With Arrow Reverse
Against Arrow Forward
8.6.2 Configure Discrete Output Polarity
Display
MenuConfigurationInputs/OutputsChannel BI/O SettingsPolarity
ProLink III Device ToolsConfigurationI/OOutputsDiscrete OutputPolarity
Field communicator Device SettingsInputs/OutputsDiscrete Output xDiscrete Output xPolarity
A Discrete Output has two states: ON (active, asserted) and OFF (inactive). Two different voltages are used to
represent these states. Discrete Output Polarity controls which voltage represents which state.
Procedure
Set Discrete Output Polarity as desired.
Default: Active High
8.6.3 Configure Discrete Output Fault Action
Display
MenuConfigurationInputs/OutputsChannel BI/O SettingsFault Action
ProLink III Device ToolsConfigurationI/OOutputsDiscrete OutputFault Action
Field communicator Process VariablesInputs/OutputsDiscrete Output xDiscrete Output xFault Action
Configuration and Use Manual Integrate the meter with the control system
MS-00809-0200-1600 May2024
Configuration and Use Manual 111