EasyManua.ls Logo

Emerson Micro Motion 1600 - 16.3 Batch troubleshooting; 16.3.1 Batch will not start; 16.3.2 Valve operation is backwards; 16.3.3 Valve does not operate

Emerson Micro Motion 1600
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. Ensure that reference temperature and reference pressure, if applicable, are configured correctly.
6. Ensure that the selected API table is appropriate for the process fluid.
16.3 Batch troubleshooting
16.3.1 Batch will not start
Cause
Previous batch not ended
Valve is closed but the transmitter is detecting flow
No discrete output configured for batch control
Active alarm(s) present
Totals were not reset
Recommended actions
1. End the batch.
2. Check for two-phase flow.
3. Verify the zero.
4. Verify the cutoffs.
5. Set up a channel to operate as a discrete output, and configure it for batch control.
16.3.2 Valve operation is backwards
Cause
Discrete Output wiring is incorrect
Discrete Output polarity is reversed
Recommended actions
1. Verify the wiring between the Discrete Output and the valve. The ON signal must open the valve.
Perform a loop test.
2. Change the setting of Discrete Output Polarity.
16.3.3 Valve does not operate
Cause
Discrete Output wiring is incorrect.
Discrete Output channel is set up for internal power. The discrete output is capable of sourcing only
7 mA. It may be necessary to switch to external power with an external power source and current limiting
resistor.
Recommended actions
1. Verify the wiring between the Discrete Output and the valve. The ON signal must open the valve.
Perform a loop test.
2. Ensure that the channel is wired and configured for external power.
3. Ensure that the valve and channel are powered.
Troubleshooting Configuration and Use Manual
May2024 MS-00809-0200-1600
178 Emerson.com

Table of Contents

Other manuals for Emerson Micro Motion 1600

Related product manuals