Label Frequency Output behavior
Internal Zero 0Hz
None (default) Determined by the setting of Process Variable Fault Action
8.6 Configure a Discrete Output
Use a Discrete Output to report specific meter or process conditions.
8.6.1 Configure Discrete Output Source
Display Menu → Configuration → Inputs/Outputs → Channel B → I/O Settings → Source
ProLink III Device Tools → Configuration → I/O → Channels → Channel B → Discrete Output
Field communicator Device Settings → Inputs/Outputs → Mapping Source → Output Source → DO x Source
Discrete Output Source specifies the process condition or device condition that is reported by a Discrete
Output.
Procedure
Set Discrete Output Source to the desired option.
Default: Forward/Reverse
Postrequisites
If you set Discrete Output Source to Flow Switch, additional configuration is required.
Related information
Configure Flow Rate Switch
Options for Discrete Output Source
Option
Label
State Discrete Output voltage
Display Prolink III
Enhanced Event 1–
5
(1)
Basic Event x Enhanced Event x ON Externally powered: Site-specific
OFF 0 V
Event 1–2
(2)
Enhanced Event x Event x ON Externally powered: Site-specific
OFF 0 V
Flow Rate Switch Flow Rate Switch Flow Switch
Indicator
ON Externally powered: Site-specific
OFF 0 V
Forward/Reverse
Indicator
Flow Direction Forward Reverse
Indicator
Forward flow 0 V
Reverse flow Externally powered: Site-specific
Calibration in
Progress
Zero in Progress Calibration in
Progress
ON Externally powered: Site-specific
OFF 0 V
Fault Fault Fault Indication ON Externally powered: Site-specific
OFF 0 V
Integrate the meter with the control system Configuration and Use Manual
May2024 MS-00809-0200-1600