Select the active concentration matrix using the display
You must select the concentration matrix to be used for measurement. Although the transmitter can store up
to six concentration matrices, only one matrix can be used for measurement at any one time.
Procedure
1. Choose MenuConfigurationProcess MeasurementConcentration MeasurementConfigure
Application.
2. Set Active Matrix to the matrix you want to use.
5.2.3 Set up concentration measurement using ProLink III
This section guides you through the tasks required to set up, configure, and implement concentration
measurement.
Enable concentration measurement using ProLink III
The concentration measurement application must be enabled before you can perform any setup. If the
concentration measurement application was enabled at the factory, you do not need to enable it now.
Prerequisites
The concentration measurement application must be licensed on your transmitter.
Disable the following applications before enabling concentration measurement as concentration
measurement cannot be enabled at the same time:
Advanced Phase Measurement — gas with liquid
API Referral
Gas Standard Volume
Procedure
1. Choose Device ToolsConfigurationProcess MeasurementFlow and ensure that Volume Flow
Type is set to Liquid Volume.
2. Choose Device ToolsConfigurationProcess MeasurementAdvance Phase MeasurementAPM
Status and ensure that Application Status is set to Disable or Liquid with Gas.
3. Choose Device ToolsConfigurationTransmitter Options.
4. Disable API Referral and set the Advance Phase Measurement application to Disabled or Single Liquid.
5. Set Concentration Measurement to Enabled and select Apply.
Load a concentration matrix using ProLink III
At least one concentration matrix must be loaded onto your transmitter. You can load up to six.
Prerequisites
The concentration measurement application must be enabled on your device.
For each concentration matrix that you want to load, you need a file containing the matrix data. The ProLink III
installation includes a set of standard concentration matrices. Other matrices are available from Emerson. The
file can be on your computer or in the transmitter internal memory.
The file must be in one of the formats that ProLink III supports. This includes:
.xml (ProLink III)
.matrix (1600)
Configure process measurement applications Configuration and Use Manual
May2024 MS-00809-0200-1600
64 Emerson.com