EasyManua.ls Logo

Emerson Micro Motion 1600 - 12.2 Perform AOC calibration; 12.2.1 Perform AOC calibration using the display; 12.2.2 Perform AOC calibration using ProLink III

Emerson Micro Motion 1600
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.2 Perform AOC calibration
AOC calibration “trains” the AOC algorithm to adjust for your network speed and valve closure speed. AOC
calibration is required only if AOC Compensation Mode is set to AOC Algorithm.
There are two options for AOC calibration:
Calculate and save: When you are satisfied with the results of AOC calibration, you can save the current
AOC coefficient. It will be used for all batches.
Rolling calibration: The AOC coefficient is recalculated for each batch, based on the results of the most
recent batches.
Prerequisites
Compensation Mode must be set to AOC. AOC only functions when the discrete output is assigned to Primary
Valve and is opening and closing an actual valve.
12.2.1 Perform AOC calibration using the display
Procedure
To calculate and save an AOC coefficient:
a) Choose MenuBatcherAOC Calibration.
b) Set AOC Cal Status to On.
c) Run several batches, allowing each batch to run to completion, and observe the totals.
d) When batch repeatability meets requirements, set AOC Cal Status to Off.
AOC calibration is stopped, and the current coefficient is saved.
Important
If you are using a saved value, repeat AOC calibration:
Whenever the fluid characteristics change, especially viscosity
Whenever you change any configuration parameter that can affect flow measurement (e.g., damping)
To set up rolling calibration:
a) Choose MenuOperationsBatcherAOC Calibration.
b) Set AOC Window to the number of batches that the rolling AOC coefficient will be based on.
c) Set AOC Cal Status to On.
Important
If you are using rolling calibration, and fluid characteristics change or the transmitter configuration
changes, the transmitter will automatically adjust to the new conditions after a few batches.
12.2.2 Perform AOC calibration using ProLink III
Procedure
To calculate and save an AOC coefficient:
a) Choose Device ToolsApplication ControlBatcherRun Batcher.
b) Click Start AOC Calibration.
c) Run several batches, allowing each batch to run to completion, and observe the totals. To set up
rolling calibration, choose Device ToolsApplication ControlBatchingRun Batcher.
Operation using the batcher Configuration and Use Manual
May2024 MS-00809-0200-1600
134 Emerson.com

Table of Contents

Other manuals for Emerson Micro Motion 1600

Related product manuals