16.9.4 Frequency Output goes in and out of fault conditions
Cause
There is a problem with the interaction between the Output Saturated alert and the fault action configured for
the output.
Recommended actions
1. Change the severity of the Output Saturated alert from Fault to another option.
2. Configure the transmitter to ignore the Output Saturated alert or the relevant conditions.
3. Change the configuration of Fault Action from Downscale to another option.
16.10 mA Output troubleshooting
16.10.1 No mA Output
Cause
Output not powered
Power supply problem
Wiring problem
Circuit failure
Recommended actions
1. If applicable, check the output wiring to verify that the output is powered.
2. Check the power supply and power supply wiring.
3. Verify the output wiring.
4. Check the Fault Action settings.
5. Verify channel configuration for the affected mA Output.
6. Measure DC voltage across output terminals to verify that the output is active.
7. Contact customer service.
16.10.2 Loop test failed
Cause
Output not powered
Power supply problem
Wiring problem
Circuit failure
Recommended actions
1. Check the power supply and power supply wiring.
2. Verify the output wiring.
3. Check the Fault Action settings.
4. Verify channel configuration for the affected mA Output.
5. Contact customer service.