Cause
The transmitter has detected moderate two-phase flow.
Recommended actions
Check your process conditions against the values reported by the device.
16.11.45 No Permanent License
Alert
Configuration warning
Cause
A permanent license has not been installed in the transmitter firmware.
Recommended actions
1. If you have a permanent license, install it.
2. If you do not have a permanent license, contact customer service.
16.11.46 Password Not Set
Alert
Configuration Error
Cause
Display security has been enabled but the display password has not been changed from the default value.
Recommended actions
Configure a password or disable display security.
16.11.47 Severe Two Phase Flow
Alert
Process Aberration
Cause
The transmitter has detected severe two-phase flow.
Recommended actions
Check your process conditions against the values reported by the device.
16.11.48 Time Not Entered
Alert
Configuration Error
Cause
The system time has not been entered. The system time is required for diagnostic logs.
Recommended actions
Set the system time.
Configuration and Use Manual Troubleshooting