Option Description
The event occurs when the value of the assigned process variable (x) is in range,
that is, between Setpoint A and Setpoint B, endpoints included.
OUT x ≤ A or x ≥ B
The event occurs when the value of the assigned process variable (x) is out
of range, that is, less than Setpoint A or greater than Setpoint B, endpoints
included.
4. Set values for the required setpoints.
• For HI and LO events, set Setpoint A.
• For IN and OUT events, set Setpoint A and Setpoint B.
5. Optional: Configure a Discrete Output to switch states in response to the event status.
6. Optional: Specify the action or actions that the transmitter will perform when the event occurs.
Option
Description
Display Menu → Configuration → Alert Setup → Enhanced Events, select any
enhanced event, and choose Assign Actions
ProLink III Device Tools → Configuration → I/O → Inputs → Action Assignment
Field communicator Device Settings → Alerts → Alert Setup → Enhanced Events
Options for Enhanced Event Action
Action
Label
Display ProLink III Field communicator
Standard
Start sensor zero Start Zero Calibration Start Sensor Zero Start Sensor Zero
Totalizers
Start/stop all totalizers and
inventories
Start/stop all totalizers Start or Stop All Totalizers Start/Stop All Totals
Reset totalizer X Reset Total X Totalizer X Reset Total X
Reset all totalizers and
inventories
Reset All Totals Reset All Totals Reset All Totals
Concentration measurement
Increment CM matrix Increment Matrix Increment ED Curve Increment Curve
Smart Meter Verification
Start Meter Verification test Start Smart Meter
Verification
6.5 Configure totalizers and inventories
Display
Menu → Configuration → Process Measurement → Totalizers & Inventories
ProLink III Device Tools → Totalizer Control → Totalizers
Configuration and Use Manual Configure advanced options for process measurement
MS-00809-0200-1600 May2024
Configuration and Use Manual 75