Discrete Output Fault Action controls the behavior of a Discrete Output if the transmitter detects a fault
condition.
Important
The fault action is implemented only if Alert Severity is set to Failure. If Alert Severity is set to any other
option, the fault action is not implemented.
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
NOTICE
Do not use Discrete Output Source as a fault indicator. If you do, you may not be able to distinguish a fault
condition from a normal operating condition. If you want to use the Discrete Output as a fault indicator, see
Fault indication with a Discrete Output.
Procedure
Set Discrete Output Fault Action as desired.
Default: None
Related information
Interaction between Process Variable Fault Action and other fault actions
Options for Discrete Output Fault Action
Label
Discrete Output behavior
Polarity=Active High Polarity=Active Low
Upscale Fault: Discrete Output is ON (site-specific
voltage)
No fault: Discrete Output is controlled by
its assignment
Fault: Discrete Output is OFF (0 V)
No fault: Discrete Output is controlled by
its assignment
Downscale Fault: Discrete Output is OFF (0 V)
No fault: Discrete Output is controlled by
its assignment
Fault: Discrete Output is ON (site-specific
voltage)
No fault: Discrete Output is controlled by
its assignment
None (default) Discrete Output is controlled by its assignment
Fault indication with a Discrete Output
To indicate faults via a Discrete Output, set Discrete Output Source to Fault. Then, if a fault occurs, the
Discrete Output is always ON and the setting of Discrete Output Fault Action is ignored.