d) When batch repeatability meets requirements, click Save AOC Calibration.
AOC calibration is stopped, and the current coefficient is saved.
Important
If you are using a saved value, repeat AOC calibration:
Whenever the fluid characteristics change, especially viscosity
Whenever you change any configuration parameter that can affect flow measurement (e.g., damping)
To set up rolling calibration:
a) Choose Device ToolsConfigurationBatcher.
b) Set AOC Window Length to the number of batches that the rolling AOC coefficient will be based on.
c) Choose Device ToolsApplication ControlRun Batcher.
d) Click Start AOC Calibration.
Important
If you are using rolling calibration, and fluid characteristics change or the transmitter configuration
changes, the transmitter will automatically adjust to the new conditions after a few batches.
Configuration and Use Manual Operation using the batcher
MS-00809-0200-1600 May2024
Configuration and Use Manual 135