Note
The default byte order is 1.
See the following table for the bit structure of bytes 1–8.
Table 9-3: Bit structure of double-precision bytes
Byte Bits Definition
1 SEEEEEEE S=Sign
E=Exponent
2 EEEEMMMM E=Exponent
M=Mantissa
3–8 MMMMMMMM M=Mantissa
5. Optional: Set Additional Communications Response Delay in delay units.
A delay unit is ⅔ of the time required to transmit one character, as calculated for the port currently in
use and the character transmission parameters.
Additional Communications Response Delay is used to synchronize Modbus communications with
hosts that operate at a slower speed than the device. The value specified here will be added to each
response the device sends to the host.
Default: 0
Range: 0 to 255
Tip
Do not set Additional Communications Response Delay unless required by your Modbus host.
Configuration and Use Manual Configure digital communications
MS-00809-0200-1600 May2024
Configuration and Use Manual 119