CIBANO 500 PTM User Manual
270 OMICRON
3. Make sure that all cable connectors are clean and dry before being tightly connected.
4. Connect CIBANO 500 to the circuit breaker for all phases according to the wiring diagram displayed
in Primary Test Manager and as shown by the following figure.
B4
Trigger IN
1
or Disabled
Iclamp4
Generic
Trip
all
Phase A
Phase B
Phase C
Close
all
Phase A
Phase B
Phase C
Motor
all
Phase A
Phase B
Phase C
1. Trigger signal starting the measurement
NOTICE
Equipment damage or loss of data possible
Never connect CIBANO 500 between the respective AUX contacts of the trip and close coils and the
coils themselves since these contacts assure that the voltage is not applied too long to the coils.
Table 18-1: Hardware configuration options of CIBANO 500 (continued)
CIBANO 500 Option