Configuration SECTION 14 Standard Web Pages
224
14-4 Configuration
At least 1 of the users configured for a CX-Supervisor application must have
web access rights in order to 'log on' to the standard web pages. To configure
web access for a particular user, the 'Allow web access for this user' option
must be ticked within the 'Configure Users' dialog box. This user will then be
able to 'log on' to the web pages remotely using their login name and
password.
14-5 Default Port
The default port for the standard web pages is 4140. If this conflicts with
another application on your machine it can be changed by running the
Standard Web Page Configuration tool.
14-6 DCOM Settings
The CX-Supervisor runtime and the web server program use Windows DCOM
to communicate with each other. If there is a problem with the DCOM settings
the Standard Web Pages login page will show 'Unknown project' instead of the
project name.
To check the DCOM
settings follow the steps
below:
1. Click Start, Run, type dcomcnfg and then click OK.
2. Expand Component Services, Computers, DCOM Config.
3. Find the entry for scs.exe and open its properties dialog box.
4. On the Identity Tab select The Interactive User.
5. Select Customize on the Security Tab of the Launch and Activation
Permissions section.
6. Click Edit and then add the user PCNAME\everyone. Select Local
Launch and Local Activation and then click OK.
7. Select Customize on the Security Tab of the Access Permissions
section.
8. Click Edit and then add the user PCNAME\everyone. Select Local
Access and then click OK. Error Pages
14-7 Error Pages
The Standard Web Pages use a two-tier error reporting system. Remote
users, that is someone viewing the web pages from any other machine apart
from the one which is running the CX-Supervisor runtime, see the default error
page. If you are viewing the web pages on the local host, a full error page is
shown. This page is not shown to remote users for security reasons.
14-8 Limitations
The standard web pages require version 3.5 or later of the Microsoft .NET
Framework to be installed on the 'server' (the computer running the CX-
Supervisor runtime application). Requirements for the client are simply a
relatively modern browser with cookies and JavaScript enabled.

Table of Contents

Other manuals for Omron CX-Supervisor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CX-Supervisor and is the answer not in the manual?

Omron CX-Supervisor Specifications

General IconGeneral
BrandOmron
ModelCX-Supervisor
CategorySoftware
LanguageEnglish

Related product manuals