Appendix D CX-Server Error Codes
305
Appendix D
CX-Server Error Codes
When errors occur in the communication package, CX-Server, an error code
may be displayed in the CX-Supervisor Error Log. To explain the cause of this
error:
• In the CX-Supervisor Error log, press the "Display Code Converter" button
to launch the Error converter and show further details. See Chapter 6
Projects, Events / Error messages for more details.
• Launch the Error Code converter from the Start menu, under the CX-
Supervisor menu and type in the code displayed.
Alternatively, the full list of causes is below.
Note: The cause is only the last 2 digits of the error code for example, if the error
shown is "0x8a1b" then ignore the "8a" and just look up "0xnn1b":
Code Cause
0xnn00 Normal Operation.
0xnn01 Cancel Button was pressed.
0xnn02 Normal Operation.
0xnn03 The executing function was stopped in the applications callback
handler.
0xnn04 The return specified buffer is not large enough to hold all the
data requested.
0xnn05 The specified name is not unique within the open project file.
0xnn06 An unspecified error occurred in CX-Server that is not handled
by any other error code.
0xnn07 CX-Server has not been initialised by the application.
0xnn08 The specified address is invalid for the selected or open device.
This error may be generated by the Communications Manager
during address validation, or the device during a read / write
request.
0xnn09 The CDMPLCCommand function executed is not supported on
the selected or open device.
0xnn0A The File or filename specified is invalid or could be opened /
created.
0xnn0B The device's operating mode is invalid for the requested
operation, or the device was opened in an mode not compatible
with the requested operation e.g attempt to execute
CDMGetData when the device was open in Read Only mode.
0xnn0C The specified name is invalid, it name contains invalid
characters.
0xnn0D One or more of the specified parameters are invalid.
0xnn0E The open PLC handle specified is invalid.
0xnn0F The open Project handle specified is invalid.
0xnn10 The open User handle specified is invalid.
0xnn11 The Key specified is invalid or cannot be found.

Table of Contents

Other manuals for Omron CX-Supervisor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CX-Supervisor and is the answer not in the manual?

Omron CX-Supervisor Specifications

General IconGeneral
BrandOmron
ModelCX-Supervisor
CategorySoftware
LanguageEnglish

Related product manuals