Troubleshooting Section 9-2
Errors occurring in
Slaves equipped with
the External Load Dis-
connected Detection
function
DRT2-OD16SLH(-1)
DRT2-OD32SLH(-1)
DRT2-MD32SLH(-1)
The Load Disconnected Flag is
going ON for outputs that are
not being used.
The Load Disconnected
Detection function may not be
disabled for the outputs that
are not being used.
Disable the Load Discon-
nected Detection function for
outputs that are not being
used.
The Load Disconnected Flag is
going ON for an output even
though the load is connected.
The load’s current consump-
tion is too low. (The minimum
output current is 3 mA.)
Disable the Load Discon-
nected Detection function.
(The function cannot detect
disconnection of this load.)
A disconnection was corrected
after being detected by the
external load disconnected
detection function, but the Load
Disconnected Flag does not go
OFF.
The function is set for manual
reset. (The default setting is
manual reset.)
After correcting the discon-
nection, turn the I/O power
supply OFF and then ON
again.
Model Details Probable cause Remedy