117 HD-1500 Platform User's Manual 31500-000 Rev A
3.7 Installing the Charging Station
Description Specification
Short circuit current rating (SCCR) 5 kA
Branch circuit protection current 25 A
Type/material of Conductors (user-sup-
plied)
Copper conductors only
The following figures provide the wiring connection configuration of the facility to the elec-
trician access box.
WARNING: ELECTRICALSHOCKRISK,FIRERISK
You must configure, and connect the facility wiring to the electrician access box
according to Figure 3-69. Wiring misconfiguration could potentially result in
electric shock or fire.
Wiring Specifications
l
Power is provided to the power supplies inside the electrician access box as (3) distinct
phases derived from (3) phase input.
l
Power supplies can withstand up to 305 VAC (nominal 277 VAC) on any given phase.
l
Configuration depends on (3) phase scheme and voltage.
l
Earth ground is separate, and always only ties to the ground distribution block.
l
White wires are used to configure for delta or WYE input.
l
Neutral terminal block accepts an abandoned neutral wire for the low voltage wye con-
figuration.
l
All field phase wires land into main disconnect switch. They do not directly go into the
terminal.