Omron SYSDRIVE 3G3RV Series User Manual

Omron SYSDRIVE 3G3RV Series
446 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
D
ifferences
by
Model
1
-
5
Table
1.4
Differences
in
Software
(Continued)
Name Parameter
Number Asia
Europe
suffixed
-E
Torque
value
setting
C4-03
to
C4-05
Disabled
C4-03/C4-04:
Set
the
rated
torque
of
the
motor.
C4-05:
Set
the
time
constant
(ms)
for
the
rising
start
torque
value.
Note:
The
filter
is
disabled
if
set
between
0
ms
and
4
ms.
Motor
constant
E1/E3
Factory
setting
200-V
class
=
200
V
60
Hz
400-V
class
=
400
V
60
Hz
Factory
setting
200-V
class
=
200
V
50
Hz
400-V
class
=
400
V
50
Hz
PG
constant F1-01
Factory
setting
600
pulses/rotation
Factory
setting
1024
pulses/rotation
Display
unit
selec-
tion
for
current
moni-
tor
F6-05 Disabled
Setting
range
0
to
1
0:
Amperage
display
1:
100%
for
8192
Multi-function
inputs H1-01
to
H1-05
Setting
range:
0
to
68
69
and
6A:
Disabled
Setting
range:
0
to
6
A
69:
JOG2
6A:
Drive
Enable
0
to
68:
Same
for
all
models
Multi-function
out-
puts
H2-02
Terminal
P1
function
select
Terminal
M3-M4
function
select
(Transistor
output)
H2-03
Terminal
P2
function
select
Terminal
M5-M6
function
select
(Transistor
output)
Signal
select
termi-
nal
A1
(voltage)
H3-01
Disabled
with
0
setting.
0:
Vo l t ag e
Limit
enabled
unchange-
able
Setting
range:
0
or
1
0:
Voltage
Limit
enabled
1:
Voltage
Limit
disabled
Gain
(terminal
FM) H4-02
Setting
range
0.0
to
2.5
Factory
setting
1.00
Setting
range
0.0
to
1000.0%
Factory
setting
100.0%
Gain
(terminal
AM) H4-05
Setting
range
0.0
to
2.5
Factory
setting
0.50
Setting
range
0.0
to
1000.0%
Factory
setting
50.0%
Bias
(terminal
FM) H4-03
Setting
range
-10.0%
to
+10.0%
Setting
range
-110.0%
to
+110.0%
Bias
(terminal
AM) H4-06
Setting
range
-10.0%
to
+10.0%
Setting
range
-110.0%
to
+110.0%
Analog
output
1
signal
level
selection
H4-07 Setting
range:
0
to
1 Setting
range:
0
to
2
Analog
output
2
sig-
nal
level
selection
H4-08
0:
0
to
+10
V
1:
-10
to
+10
V
0:
0
to
+10
V
1:
-10
to
+10
V
2:
4
to
20
mA
Frequency
reference
for
loss
of
frequency
reference
L4-06
Uses
the
factory
setting
value
(80%)
and
unchangeable.
Set
reference
frequency
for
operation
when
frequency
lost.
The
output
frequency
is
(Specified
Frequency)
x
L4-06.
Input
open-phase
pro-
tection
selection
L8-05
Factory
setting
0
(Disabled)
Factory
setting
1
(Enabled)
Output
open-phase
protection
selection
L8-07
Factory
setting
0
(Disabled)
Factory
setting
1
(Enabled)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish