RFC 4072S
158 / 272
PHOENIX CONTACT 108580_en_02
Figure 6-2 Standard controller in the “STOP” state
• Double-click on the “Safety PLC” node in the “PLANT” area.
The editor group of the safe PLC opens.
• Select the “Safety Cockpit” editor.
• Click on the button to connect PLCnext Engineer to the safe PLC.
• Click on the button to switch to the debug mode of the iSPNS3000.
• Acknowledge the following message to switch to debug mode of the SPNS.
Figure 6-3 PLCnext Engineer safety prompt: switching to debug mode
WARNING: Excluding hazards
Switching to debug mode means that you will exit normal mode.
Make sure that your system/machine cannot pose a hazard to people or equipment.