Rexroth IndraDrive Fusing and Selecting the Mains Contactor 13-3
DOK-INDRV*-SYSTEM*****-PR02-EN-P
Device Mains
choke
Mains
input
contin.
current
I
L,cont
Min. nominal fuse
current of characteristic
Autom.
circuit-
breaker
Power
circuit-
breaker
Min. line
cross
section@
Ta40°
Recom-
mended
mains
contactor
Max.
allowed
switch-
off
delay
[A] eff
@ P
DC
cont
[A] [A] [A] [A]
(setting
value)
[mm²]
([AWG])
Type [ms]
Properties
gR gL tripping
charact.
C
HMV01.1
E
HNL01.1
W0030 without 31 -- 35 32 31 6 (8) integrated -
W0030 with 51 -- 63 63 51 16 (6) integrated -
W0075 without 77 -- 100 -- 77 25 (2) integrated -
W0075 with 128 -- 160 -- 128 70 (1/0) integrated -
W0120 without 123 -- 160 -- 123 50 (1/0) integrated -
W0120 with 204 -- 250 -- 204 120
(0000)
integrated -
HMV01.1
R
HNL01.1
W0018 with 26 -- 35 32 26 6 (10) integrated -
W0045 with 65 -- 80 -- 65 25 (4) integrated -
W0065 with 94 -- 125 -- 94 35 (2) integrated -
tbd: in preparation
Fig. 13-1: Fusing and selection of mains contactor 3AC400V