13-4 Fusing and Selecting the Mains Contactor Rexroth IndraDrive
DOK-INDRV*-SYSTEM*****-PR02-EN-P
Mains voltage 3 AC 480 V
Device Mains
choke
Mains
input
contin.
current
I
L,cont
Min. nominal fuse
current of characteristic
Autom.
circuit-
breaker
Power
circuit-
breaker
Min. line
cross
section@
Ta40°
Recom-
mended
mains
contactor
Max.
allowed
switch-
off
delay
[A] eff
@ P
DC
cont
[A] [A] [A] [A]
(setting
value)
[mm²]
([AWG])
Typ [ms]
Properties
gR gL tripping
charact.
C
HCS03.1E HNK01.1
W0070 without tbd tbd tbd - - tbd tbd tbd
W0070 with 42
Littelfuse
L50S50*
Cooper-
Bussmann
FWH-50B*
3NA6..820 - - 16 (6) 3RT10 44 180
W0100 without tbd tbd tbd - - tbd tbd tbd
W0100 with 67
Littelfuse
L50S70*
Cooper-
Bussmann
FWH-70B*
3NA6..824 - - 35 (4) 3RT10 44 350
W0150 without tbd tbd tbd - - tbd tbd tbd
W0150 with 88
Littelfuse
L50S100*
Cooper-
Bussmann
FWH-100B*
3NA6..830 - - 50 (2)
2x25 (2)
3RT10 46 350
W0210 without tbd tbd tbd - - tbd tbd tbd
W0210 with 122
Littelfuse
L50S125*
Cooper-
Bussmann
FWH-125B*
3NA6..832 - - 95 (1/0)
2x50 (1/0)
3RT10 55 350
HCS02.1E HNL01.1
W0012 without 6 -- 10 10 8 1,0 (16) 3RT1016 80
W0012 with 6 -- 10 10 8 1,0 (16) 3RT1016 80
W0028 without 13 -- 20 20 17 2,5 (13) 3RT1025 110
W0028 with 13 -- 20 20 17 2,5 (13) 3RT1025 110
W0054 without 19 -- 25 25 25 4,0 (11) 3RT1026 190
W0054 with 19 -- 25 25 25 4,0 (11) 3RT1026 190
W0070 without 30 -- 35 32 35 6,0 (9) 3RT1034 120
W0070 with 30 -- 35 32 35 6,0 (9) 3RT1034 120