13-6 Fusing and Selecting the Mains Contactor Rexroth IndraDrive
DOK-INDRV*-SYSTEM*****-PR02-EN-P
Mains voltage 3 AC 500 V
Device Mains
choke
Mains
input
contin.
current
I
L,cont
Min. nominal fuse
current of characteristic
Autom.
circuit-
breaker
Power
circuit-
breaker
Min. line
cross
section@
Ta40°
Recom-
mended
mains
contactor
Max.
allowed
switch-
off
delay
[A] eff
@ P
DC
cont
[A] [A] [A] [A]
(setting
value)
[mm²]
([AWG])
Typ [ms]
Properties
gR gL tripping
charact.
C
HCS03.1E HNK01.1
W0070 without tbd tbd tbd - - tbd tbd tbd
W0070 with 40 3NE1802-0 3NA6817 - - 16
(6)
3RT1044 180
W0100 without tbd tbd tbd - - tbd tbd tbd
W0100 with 64 3NE1820-0 3NA6824 - - 25
(4)
3RT1044 350
W0150 without tbd tbd tbd - - tbd tbd tbd
W0150 with 85 3NE1021-0 3NA6830 - - 2x25/50
(2)
3RT1046 350
W0210 without tbd tbd tbd - - tbd tbd tbd
W0210 with 117 3NE1022-0 3NA6832 - - 2x50/95
(1/0)
3RT1055 350
HCS02.1E HNL01.1
W0012 without 6 -- 10 10 8 1,0 (16) 3RT1016 80
W0012 with 6 -- 10 10 8 1,0 (16) 3RT1016 80
W0028 without 13 -- 20 20 17 2,5 (13) 3RT1025 110
W0028 with 13 -- 20 20 17 2,5 (13) 3RT1025 110
W0054 without 19 -- 25 25 25 4,0 (11) 3RT1026 190
W0054 with 19 -- 25 25 25 4,0 (11) 3RT1026 190
W0070 without 30 -- 35 32 35 6,0 (9) 3RT1034 120
W0070 with 30 -- 35 32 35 6,0 (9) 3RT1034 120
tbd: in preparation
Fig. 13-3: Fusing and selection of mains contactor 3AC500V