Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-27
D.3.11 Data record 96 – maximum pointers
ID no. Byte Meaning Value range /
[coding]
Increment Note
Maximum pointers
651 14…15 Number of motor overload
trippings
0… 65535 1 —
652 12…13 Max. tripping current I
A max(%)
0…1000% 3.125% 9-bit current for-
mat
653 8 Phase current I
L1 max(%)
0…796.9% 3.125% 8-bit current for-
mat
654 9 Phase current I
L2 max(%)
0…796.9% 3.125% 8-bit current for-
mat
655 10 Phase current I
L3 max(%)
0…796.9% 3.125% 8-bit current for-
mat
656 4 Phase current I
L1 min(%)
0…796.9% 3.125% 8-bit current
format
657 5 Phase current I
L2 min(%)
0…796.9% 3.125% 8-bit current
format
658 6 Phase current I
L3 min(%)
0…796.9% 3.125% 8-bit current
format
659 16...19 Max. tripping current
I
A max(eff)
±0...20 A 0.01 A —
660 32...35 Phase current I
L1 max(eff)
±0...20 A 0.01 A —
661 36...39 Phase current I
L2 max(eff)
±0...20 A 0.01 A —
662 40...43 Phase current I
L3 max(eff)
±0...20 A 0.01 A —
663 20...23 Phase current I
L1 min(eff)
±0...20 A 0.01 A —
664 24...27 Phase current I
L2 min(eff)
±0...20 A 0.01 A —
665 28...31 Phase current I
L3 min(eff)
±0...20 A 0.01 A —
666 44...45 Reserved = 0
667 46...47 Reserved = 0
668 48...49 Reserved = 0
669 50...51 Reserved = 0
670 52...53 Reserved = 0
671 54...55 Reserved = 0
672 56...57 Reserved = 0
673 58...59 Reserved = 0
674 60 Reserved = 0
675 61 Reserved = 0
676 62 Reserved = 0
677 63 Reserved = 0
Table D-15: Data record 96 – maximum pointers