EasyManua.ls Logo

Siemens SIMATIC ET 200pro - Page 239

Siemens SIMATIC ET 200pro
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-27
D.3.11 Data record 96 – maximum pointers
ID no. Byte Meaning Value range /
[coding]
Increment Note
Maximum pointers
651 14…15 Number of motor overload
trippings
0… 65535 1
652 12…13 Max. tripping current I
A max(%)
0…1000% 3.125% 9-bit current for-
mat
653 8 Phase current I
L1 max(%)
0…796.9% 3.125% 8-bit current for-
mat
654 9 Phase current I
L2 max(%)
0…796.9% 3.125% 8-bit current for-
mat
655 10 Phase current I
L3 max(%)
0…796.9% 3.125% 8-bit current for-
mat
656 4 Phase current I
L1 min(%)
0…796.9% 3.125% 8-bit current
format
657 5 Phase current I
L2 min(%)
0…796.9% 3.125% 8-bit current
format
658 6 Phase current I
L3 min(%)
0…796.9% 3.125% 8-bit current
format
659 16...19 Max. tripping current
I
A max(eff)
±0...20 A 0.01 A
660 32...35 Phase current I
L1 max(eff)
±0...20 A 0.01 A
661 36...39 Phase current I
L2 max(eff)
±0...20 A 0.01 A
662 40...43 Phase current I
L3 max(eff)
±0...20 A 0.01 A
663 20...23 Phase current I
L1 min(eff)
±0...20 A 0.01 A
664 24...27 Phase current I
L2 min(eff)
±0...20 A 0.01 A
665 28...31 Phase current I
L3 min(eff)
±0...20 A 0.01 A
666 44...45 Reserved = 0
667 46...47 Reserved = 0
668 48...49 Reserved = 0
669 50...51 Reserved = 0
670 52...53 Reserved = 0
671 54...55 Reserved = 0
672 56...57 Reserved = 0
673 58...59 Reserved = 0
674 60 Reserved = 0
675 61 Reserved = 0
676 62 Reserved = 0
677 63 Reserved = 0
Table D-15: Data record 96 – maximum pointers