Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-35
—49
0…7
Stop voltage 20% ... 90% 5% 40%
sDSSte/sDSte,
sRSSte/sRSte
—50
0…7
Current limitation
value
125% ... 600%
3.125%
600%
sDSSte/sDSte,
sRSSte/sRSte
—51
0…3
Type of start-up Direct [0]
Voltage ramp [1]
Current limitation [4]
Voltage ramp and
current limitation [5]
—[0]
sDSSte/sDSte,
sRSSte/sRSte
—51
4…7
Type of coasting
down
free run-down [0]
voltage ramp [1]
—[0]
sDSSte/sDSte,
sRSSte/sRSte
52 Substitute value
(byte 0)
see PAA [0]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
53 Substitute value
(byte 1)
54…55 Disabled Not used
—56
0…2
Disabled Not used
—56
3
Status alarm Not used
—56
4
Update alarm Not used
—56
5
Process alarm Not used
3
0
56
6
Group diagnosis disable [0]
enable [1]
—[0]
all starters
3
3
56
7
Response to CPU /
Master STOP
Substitute value [0]
switch [1]
—[0]
all starters
—57
0-1
Reserved Not used
3
1
57
2
General warning
diagnosis
disable [0]
enable [1]
—[0]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
3
2
57
3
Wait for start-up
parameter data
no [0]
yes [1]
—[0]
all starters
—57
4…6
Safe tripping group
(F reference)
Not used
—57
7
Reserved
58…59 Brake release delay
on starting
–2.5…2.5 s 10 ms 0 s all ....-AA3
starters
60…61 Brake hold time on
stopping
0…25 s 10 ms 0 s all ....-AA3
starters
ET 200
pro
RPM
Byte
No.
DS 131
Byte no.
Parameters Value range
Increme
nt
Factory
setting
Relevant for
Table D-18: Data record 131device parameters (Continued)