Data formats and data records
SIMATIC - ET 200pro motor starter
D-34 GWA 4NEB 950 5661-02 DS 04
4
0…3
39
0…3
Input 1 – action No action [0]
Tripping without
restart [1]
Tripping with restart
[2]
Tripping end position
clockwise [3]
Tripping end position
counter-clockwise
[4]
General warning [5]
Manual local operat-
ing mode [6]
Emergency start [7]
Motor CLOCKWISE
[8]
Motor COUNTER-
CLOCKWISE [9]
(only RSe)
Quick stop [11]
Trip reset [12]
[ 13…15] free
4
4…7
39
4…7
Input 2 – action
5
0…3
40
0…3
Input 3 – action
5
4…7
40
4…7
Input 4 – action
Make / break con-
tact
Make / break con-
tact
Make / break con-
tact
Make / break con-
tact
Make contact
Make contact
Make contact
Make contact
Make contact
Make / break con-
tact
Make contact
—[0]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
—41
0
Input 1 – signal not latching [0]
latching [1] [0]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
—41
1
Input 2 – signal
—41
2
Input 3 – signal
—41
3
Input 4 – signal
—41
4…7
Reserved —
—42
0…7
Brake release delay
time on starting
Not used
—43
0…7
Brake hold time on
stopping
Not used
—44
0…7
Braking time Not used
—45
0…7
Braking torque Not used
—46
0…7
Startup time 0 ... 30 s 0.25 s 5 s
sDSSte/sDSte,
sRSSte/sRSte
—47
0…7
Run-down time 0 ... 30 s 0.25 s 0 s
sDSSte/sDSte,
sRSSte/sRSte
—48
0…7
Start voltage 20% ... 100% 5% 40%
sDSSte/sDSte,
sRSSte/sRSte
ET 200
pro
RPM
Byte
No.
DS 131
Byte no.
Parameters Value range
Increme
nt
Factory
setting
Relevant for
Table D-18: Data record 131 – device parameters (Continued)