Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-33
7
7
32
6
Response to cur-
rent limit violation
warning [0]
tripping [1]
—[0]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
7
6
32
7
Response to resid-
ual current detection
warning [0]
tripping [1]
—[1]
all starters
—33
0…1
Response to circuit
breaker off
Not used
—33
2…3
Response to over-
load switching ele-
ment
Not used
—33
4…7
Asymmetry pre-
warning limit value
Not used
—34
0…2
Asymmetry limit
value
30%…60% 10% 30%
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
—34
3…5
Reserved —
7
3
34
6
Response to
asymmetry
warning [0]
tripping [1]
—[1]
all starters
—34
7
Response to earth
fault
Not used
—35
0…7
Earth fault pre-
warning limit value
Not used
—36
0…7
Lock-out time 0s…60s 1s 0s RSe (HF),
sRSSte/
sRSte
—37
0…7
Input signal exten-
sion
0…200 ms 10 ms 0 ms
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
—38
0…2
Input signal delay 10…80 ms 10 ms 10 ms
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
—38
3
Input quick stop –
level
Not used
3
4
38
4
Input 1 – level Break contact
[0]
Make contact
[1]
—[1]
DSe, RSe (HF);
sDSSte/sDSte,
sRSSte/sRSte
3
5
38
5
Input 2 – level
3
6
38
6
Input 3 – level
3
7
38
7
Input 4 – level
ET 200
pro
RPM
Byte
No.
DS 131
Byte no.
Parameters Value range
Increme
nt
Factory
setting
Relevant for
Table D-18: Data record 131 – device parameters (Continued)