9.1 General information
9-220
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
!
Warning
If the electronics power supply of the NE or monitoring module is connected
directly in front of the commutating reactor at the line supply, 6–conductor con-
nection, via terminals 2U1–2V1–2W1, then it is not
permissible to connect
X181: P500/M500 to the DC link P600/M600, refer to Section 9.13.
!
Warning
To shut down in a controlled fashion using the DC link energy at power failure,
e.g. terminal P500/M500 can for example, remain connected to the DC link
P600/M600.
When powering down using the line contactor, or in the setting–up mode, this
connection must be reliably and safely disconnected, e.g. using a contactor
with ”protective separation” refer to Section 9.12.
!
Warning
For a six conductor connection of the NE module, and where the electronic
supply is connected directly to the line supply, the jumpers, inserted in connec-
tor X181 at the NE module when the equipment is supplied, must be removed,
refer to Section 9.13.
!
Warning
The connections at the input and output side at the line filter may not be inter-
changed.
9 Important Circuit Information