IEC60364‑5‑52:2019Section524 makes recommendations for sizing the neutral conductor.
If no more precise inf
ormation is available, the standard recommends dimensioning the
neutral conductor for 1.45 times the current-carrying capacity of the line conductors.
WARNING
Fire caused by neutral conductor (N) overload
The neutral conductor can heat up due t
o the load from harmonic currents and cause a 󹪝re.
Consider the harmonic currents when dimensioning the neutral conductor.
WARNING
Electric shock caused by PEN conductor overload
In TN-C supply netw
orks, the protective function of the PEN conductor can be adversely
a󹪜ected by exposure to harmonic currents.
Consider the harmonic currents when dimensioning the PEN conductor.
Connecting
6.4Connecting the mains supply
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
134 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB